Advanced Analog Alarm Settings

The advanced Analog Alarm Settings window expands the basic alarm settings options to up to five
severity levels.

Configure the following parameters:

Send Syslog Alert

When enabled, sends a message to syslog when an alarm is triggered or
cleared. The syslog entry includes the severity level and the value that caused
the alarm to trigger or clear. The syslog message is associated with

Level

Critical

.

Default: Disabled

Send SNMP Alert

When enabled, sends an SNMP trap when an alarm is triggered or cleared. The
trap consists of the severity level and whether the alarm was triggered or
cleared.

Default: Disabled

Trigger Type

If the

Trigger Type

is

Low

, an alarm is triggered when the input drops below

the specified

Trigger

value; other severity level trigger values must decrease in

value with each subsequent level. If the

Trigger Type

is

High

, an alarm is

triggered when the input is higher than the specified

Trigger

value; other

severity level trigger values must increase in value with each subsequent level.

Clear Mode

To clear an alarm, the input must drop below the specified value when

Trigger

Type

is

High

or go above the specified value when

Trigger Type

is

Low

.

Level 1-5

Defines the Level severity settings for up to five levels. If the

Trigger Type

is

Low

, an alarm is triggered when the input drops below the specified

Trigger

value; other severity level trigger values must decrease in value with each
subsequent level. If the

Trigger Type

is

High

, an alarm is triggered when the

input is higher than the specified

Trigger

value; other severity level trigger

values must increase in value with each subsequent level.