Error messages and countermeasures – Omron ZS-MDC User Manual

Page 79

Advertising
background image

5-3

ZS-MDC

User’s Manual

Section 5

APP

E

NDIX

Section 5

Error Messages and Countermeasures

Error Messages and Countermeasures

When [Error] Is Displayed on the Main Display

When all digits on the main display and sub-display blink

Others

Display Details

Cause

Countermeasure

LCD screen
(upper section)

Overcurrent

One or all of the judgment out-
puts are short-circuited.

Cancel the load short-circuit.
(Recovery is automatic after the
load short-circuit is canceled.)

Calculation data error

One (or all) of the channels
assigned to the operation input
cannot be measured.

Check the measurement state of
the channels assigned to the oper-
ation input, and set all channels to
a measurable state.

Display Details

Cause

Countermeasure

LCD screen

SYSTEM ERROR
CONNECT

The controller is not connected.

Connect the Controller.

SYSTEM ERROR
BANK DATA

Bank data in the Sensor Control-
ler in error

Hold the UP key down for 3 sec-
onds, and then hold the DOWN
key down for 3 seconds.
The sensor is turned ON again
and restored after the device is
initialized.

SYSTEM ERROR
MAIN COM

Internal error

Turn the sensor ON again.

Display Details

Cause

Countermeasure

LCD upper sec-
tion

Disp range error

The measurement result
exceeds the number of dis-
played digits.

Change the decimal point digit
setting.

Main Display

– – – – – –

• The sensor is standing by

for measurement.

• No channels are assigned

to inputs. (Assignments
are set to “NONE”.)

• When hold is set, start sam-

pling and apply the hold
value.

• Assign the channels.