Caution – Quadra-Fire MTVERNON-AE-MBK User Manual

Page 10

Advertising
background image

Page 10

7034-106F

August 13, 2009

R

Mt. Vernon Pellet Stove (AE)

R

R

B. Avoiding Smoke and Odors

Negative Pressure, Shut-Down and Electrical Power
Failure

To reduce the probability of back-drafting or burn-back in

the pellet appliance during power failure or shut down con-

ditions, it must be able to draft naturally without exhaust

blower operation.
Negative pressure in the house will resist this natural draft

if not accounted for in the pellet appliance installation.

Heat rises in the house and leaks out at upper levels. This

air must be replaced with cold air from outdoors which

flows into lower levels of the house.
Vents and chimneys into basements and lower levels of the

house can become the conduit for air supply and reverse

under these conditions.

Outside Air

An outside air kit is recommended in all installations. The

Outside Air Kit must be ordered seperately.
Per national building codes, consideration must be given

to combustion air supply to all combustion appliances.

Failure to supply adequate combustion air for all appli-

ance demands may lead to backdrafting of those and other

appliances.

When the appliance is roof vented (strongly recommended):

The air intake is best located on the exterior wall ori-

ented towards the prevailing wind direction during the

heating season.

When the appliance is side-wall vented:

The air intake is best located on the same exterior wall

as the exhaust vent outlet and located lower on the wall

than the exhaust vent outlet.

The outside air supply kit can supply most of the demands

of the pellet appliance, but consideration must be given to

the total house demand.
House demand may consume the air needed for the appli-

ance. It may be necessary to add additional ventilation to

the space in which the pellet appliance is located.
Consult with your local HVAC professional to determine the

ventilation demands for your house.

Vent Configurations
To reduce probability of reverse drafting during shut-down

conditions Hearth & Home Technologies strongly recom-

mends:

• Installing the pellet vent with a minimum vertical run

of 5 feet (1.5m). Preferably terminating above the

roof line.

• Installing the outside air kit at least  feet (1.m)

below the vent termination.

To prevent soot damage to exterior walls of the house and

to prevent re-entry of soot or ash into the house:

• Maintain specified clearances to windows, doors and

air inlets, including air conditioners.

• Vents should not be placed below ventilated soffits.

Run the vent above the roof.

• Avoid venting into alcove locations.
• Vents should not terminate under overhangs, decks

or onto covered porches.

• Maintain minimum clearance of 1 inches (05mm)

from the vent termination to the exterior wall. If you

see deposits developing on the wall, you may need

to extend this distance to accommodate your installa-

tion conditions.

CAUTION

• DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE

SERVICING ANOTHER APPLIANCE.

• DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT

OR SYSTEM.

Optional Battery Back-Up

Hearth & Home Technologies supplies an optional battery

back-up system that operates the appliance during power

failure conditions to prevent smoking. In shutdown mode,

the battery back-up will not prevent smoking. See Section
8 for details.

Hearth & Home Technologies assumes no responsibility for,

nor does the warranty extend to, smoke damage caused

by reverse drafting of pellet appliances under shut down or

power failure conditions.

Advertising