Supply fan adjustment

Use the following procedure to
determine the proper adjustment of
the supply fan for a specific
application.
1. Determine total external static

pressure about system and
accessories.

a. Obtain the design airflow rate

and the design external static
pressure drop through the
distribution system.

b. Add static pressure drop of the

accessories installed on the
unit. (Table 7,8 & 9)

c. Add the total accessory static

pressure drop (from step 1b) to
the design external static
pressure (from step 1a). The
sum of these two values is the
total system external static
pressure.

2. Using the Tables 10 through 20 to

find the external static pressure
that most closely approximates
total system external static
pressure. Then locate the
appropriate airflow rate for your
unit. The value obtained
represents the brake horsepower
for the supply fan motor and the
fan RPM.

3. Adjust motor sheave according

to Table 6.

Table 6 - Motor sheave / Fan speed

Fan Speed (RPM)

Standard Drive

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

UNIT

Open

Open

Open

Open

Open

Open

Closed

YKD/YKH 155

566

601

637

672

708

743

N/A

YKD/YKH 175

724

769

815

860

906

951

N/A

YKD/YKH 200

513

550

586

623

659

696

N/A

YKD/YKH 250

588

619

650

681

712

743

N/A

TKD/TKH 155

566

601

637

672

708

743

N/A

TKD/TKH 175

724

769

815

860

906

951

N/A

TKD/TKH 200

513

550

586

623

659

696

N/A

TKD/TKH 250

588

619

650

681

712

743

N/A

WKD/WKH 125

533

566

600

633

667

700

N/A

WKD/WKH 155

566

601

637

672

708

743

N/A

WKD/WKH 200

513

550

586

623

659

696

N/A

Fan Speed (RPM)

Oversized Drive

6 turns

5 turns

4 turns

3 turns

2 turns

1 turns

UNIT

Open

Open

Open

Open

Open

Open

Closed

YKD/YKH 155

672

714

756

798

840

882

N/A

YKD/YKH 175

791

840

890

939

989

1038

N/A

YKD/YKH 200

680

711

742

773

804

835

N/A

YKD/YKH 250

690

722

754

786

818

850

N/A

TKD/TKH 155

672

714

756

798

840

882

N/A

TKD/TKH 175

791

840

890

939

989

1038

N/A

TKD/TKH 200

680

711

742

773

804

835

N/A

TKD/TKH 250

690

722

754

786

818

850

N/A

WKD/WKH 125

724

769

815

860

906

951

N/A

WKD/WKH 155

513

550

586

623

659

696

N/A

WKD/WKH 200

588

619

650

681

712

743

N/A

Advertising