Operation

45

RT-SVX19A-E4

Thermostat signals are as follows:

R 24VAC power to thermostat

Y1 Call for compressor 1 or first
stage cooling

Y2 Call for compressor 2 or 2nd
stage cooling

G Call for supply fan

W1 Call for heat 1

W2 Call for heat 2

Heat pump only:

X2 Call for emergency heat

O Switchover valve On = cooling,
Off = heating

T Bias for heat anticipation for those
mechanical thermostats that use
this function

Conventional thermostat –
Gas/ Electric, Electric Heat:

Input/connection

Function when
energized :

G (fan)

Fan runs continuously
except during
unoccupied mode
(see next page)

Y1 (compressor 1
or economizer)

Compressor #1 runs
or economizer
operates

Y2 (compressor 2
or compressor 1
while economizing)

Compressor #2 also
runs, or #1
compressor runs
while economizing

W1 (gas / electric
heat first stage)

1st stage heat

W2 (gas / electric
heat 2nd stage)

2nd stage heat (if
available)

Conventional thermostat –
Heat Pump

T (provides heat anticipation signal for
those mechanical thermostats that use this
feature. If the thermostat used does not
have a “T” terminal, disregard this
terminal.

Input/connection

Function when
energized

Cooling mode:

G (fan)

Fan runs continuously
except during
unoccupied mode
(see next page)

O (reversing valve
during cooling)

Reversing valve in
cool mode

Y1 + O
(first stage cooling)

Compressor #1 runs
or economizer
operates

Y1 + Y2 + O
(2nd stage cool)

Compressor #2 also
runs, or #1
compressor runs
while economizing.

Heating mode:

G (fan)

Fan runs continuously
except during
unoccupied mode
(see below)

Y1 (both
compressors 1st
stage heat)

Both compressors
run

Y2 (during heating
– nothing happens)

No change

W2 (electric heat
2nd stage)

2nd stage (electric)
heat

X2 (electric heat
only)

Electric heat only –
no compressors