Table 22 - Electrical data - TKD/TKH Compressor motor and condenser motor

(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor

Table 23 - Electrical data - YKD/YKH Compressor motor and condenser motor

(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor

TKD/H

TKD/H

TKD/H

TKD/H

155

175

200

250

Compressor

Number

2

2

2

2

Type

Scroll

Scroll

Scroll

Scroll

Model

9T / 5T

10T / 6.7T

9T / 9T

10T / 10T

Rated Amps (1)

(A)

15.0 / 8.5

15.1 / 11.4

14.7 / 14.7

15.3 / 15.3

Locked rotor Amps (2)

(A)

118 / 65.5

118 / 101

118 / 118

118 / 118

Outdoor Fan

Nominal Airflow

(m

3

/h)

15350

19750

21000

23500

Type

Axial

Axial

Axial

Axial

Diameter

(mm)

660

660

710

710

Drive type

Direct

Direct

Direct

Direct

Number

2

2

2

2

Motor HP

(kW)

0.25

0.25

0.56

0.56

Motor Rated Amps (1)

(A)

1.6

1.6

2.3

2.3

Motor Locked rotor Amps (2)

(A)

3.8

3.8

5.8

5.8

Motor RPM

(rpm)

925

925

925

925

YKD/H

YKD/H

YKD/H

YKD/H

155

175

200

250

Compressor

Number

2

2

2

2

Type

Scroll

Scroll

Scroll

Scroll

Model

9T / 5T

10T / 6.7T

9T / 9T

10T / 10T

Nominal Amps (1)

(A)

15.0 / 8.5

15.1 / 11.4

14.7 / 14.7

15.3 / 15.3

Locked rotor Amps (2)

(A)

118 / 65.5

118 / 101

118 / 118

118 / 118

Outdoor Fan

Nominal Airflow

(m

3

/h)

15350

19750

21000

23500

Type

Axial

Axial

Axial

Axial

Diameter

(mm)

660

660

710

710

Drive type

Direct

Direct

Direct

Direct

Number / Voltage

2

2

2

2

Motor HP

(kW)

0.25

0.25

0.56

0.56

Motor Rated Amps (1)

(A)

1.6

1.6

2.3

2.3

Motor Locked rotor Amps (2)

(A)

3.8

3.8

5.8

5.8

Motor RPM

(rpm)

925

925

925

925

Advertising