Operation – Trane RT-SVX19A-E4 User Manual

Page 46

Advertising
background image

Operation

RT-SVX19A-E4

46

Unoccupied mode:

If the thermostat being used is
programmable, it will have its own
strategy for unoccupied mode and
will control the unit directly. If a
mechanical thermostat is being
used, a field applied time clock with
relay contacts connected to J6-11
and J6-12 can initiate an
unoccupied mode as follows:

Contacts open: Normal occupied
operation.

Contacts closed: Unoccupied
operation as follows - Fan in
auto mode regardless of fan
switch position. Economizer
closes except while economizing
regardless of minimum position
setting.

Cooling/Economizer Operation:

If unit does not have an economizer,
the Cool/Econ Stage 1 and Stage 2
will call directly for mechanical
cooling (compressor) stages. If the
unit has an economizer, the
Cool/Econ stages will function as
follows.

Table 34 - Cooling/Economizer Operation with Thermostat1,2

OK to

Economize?

Thermostat

Y1

Thermostat

Y2

Call for Economizer

Cooling

Compressor Staging

Request

No

On

Off

Inactive

Compressor Output 1

No

Off

On

Inactive

Compressor Output 2

No

On

On

Inactive

Compressor
Outputs 1 & 2

Yes

On

Off

Active

Off

Yes

Off

On

Active

Compressor off

Yes

On

On

Active

Compessor