Final installation checklist, Operation – Trane RT-SVX19A-E4 User Manual

Page 57

Advertising
background image

Final installation checklist

• Is the condenser fan and indoor

blower operating correctly, i.e.:
correct rotation and without
undue noise?

• Are the compressors operating

correctly and has the system
charge been checked?

• Has the gas module been

installed as per the procedure in
this manual?

• Have the voltage and running

currents been checked to
determine if they are with in
limits?

• Have the air discharge grilles

been adjusted to balance the
system?

• Has the ductwork been checked

for air leaks and any
condensation?

• Has the heating air temperature

rise been checked?

• Has the indoor airflow been

checked and adjusted if
necessary?

• Has the unit been checked for

tubing and sheet metal rattles
orany unusual noises?

• Are all covers and panels in

placeand properly fastened?

To keep the unit operating safely
and efficiently, the manufacturer
recommends that a qualified service
technician check the entire system
at least once each year, or more
frequently if conditions warrant.

Operation

57

RT-SVX19A-E4

Refer to the ignition control module
diagnostics section for the LED
diagnostic definitions.

When the fan selection switch is set
to the "Auto" position, the RTRM
energizes the supply fan relay (F)
coil approximately 30 second after
initiating the heating cycle to start
the supply fan motor (IDM).

The automatic reset high limit
(TCO1), located in the bottom right
corner of the burner compartment,
protects against abnormally high
leaving air temperatures.

The automatic reset fan fail limit
(TCO2), located in the upper middle
section of the supply fan board,
protects against abnormally high
heat buildup which could occur
because of extended cycling of the
high limit (TCO1) or if the supply
fan motor (IDM) fails to operate.
Should TCO2 open, the RTRM will
energize the supply fan relay (F) in
an attempt to start the fan motor.
The RTRM signals that a heat failure
has occurred by flashing the "Heat"
LED on the zone sensor.

There is a Green LED located in the
Ignition Control Module. The table
below lists the diagnostics and the
status of the LED during the various
operating states.

Table 40 -LED status

Diagnostics

Green LED

Red LED

1. Powered but no heat dernand

Off

Off

2. Heat demand without fault

Flash ing

Off

3. No flame detection on ignition - or signal detected

and then lost

Off

Flashing

4. Gas unit incorrectly wired or flame signal detected on

a heat demand

Steady

Flashing

5. Internal fault

Off

Steady