Controls – Trane RT-SVX19A-E4 User Manual

Page 34

Advertising
background image

Controls

RT-SVX19A-E4

34

Power supply requirements

CAUTION! Make sure that you
connect the power wire only to the
24V terminal. Connecting the power
wire to the output terminal may
result in equipment damage.

The CO

2

sensor is designed to

operate with a nominal 24 Vac
supply. The power supply should
maintain the voltage between 20 to
26 Vac.

Table 31 - CO

2

sensor wire size

Wiring the wall-mounted CO

2

sensor

DVC setpoint potentiometer on
economizer module can be adjusted
as follows:

0% - 500ppm, 50% - 1000 ppm,

100% - 1500ppm

The outside air damper will
modulate from minimum position
setting to up to 100% while
attempting to maintain the CO

2

setpoint.

To connect the wall mounted CO

2

sensor, Refer to the wiring diagram
provided in the unit.

Cross

section

Maximum wire

Iength

(mm2)

(mn)

0.25

50

0.5

100

1

200

Wiring the duct-mounted CO

2

sensor
1. Connect the DCV signal lwire to

the connector DCV of the ECA

2. Connect the power according to

the guidelines in Power supply
requirements.

To connect the wall mounted CO

2

sensor, Refer to the wiring diagram
provided in the unit.

Mounting the wall-mounted sensor
1. Select a proper location in the

room to mount the CO

2

sensor.

Look for an interior wall with
good air circulation,
approximately 1.4 m from the
floor.

2. Remove the back plate from the

sensor and thread the power
wires and output signal wire
through the hole in the back
plate.
For surface wiring, make cut-
outs with pliers to the thinner
section of the upper or lower
edge of the back plate and to
thread the wires through.

3. Mount the back plate to the wall

with screws. Note that the arrow
on the back plate shows the
mounting direction.

Figure 12 - Jumper settings

OUTPUT
SELECTION
JUMPERS