Operation – Trane RT-SVX19A-E4 User Manual

Page 52

Advertising
background image

Operation

RT-SVX19A-E4

52

Table 37 - Marking category of the gas section in different countries

Table 38 - Gas burner data

Country

FR

CH+ES-GB-IE-PT

IT

NL

BE

LU-DE

AT-DK-Fl-SE

Category

II2E+3P

II2H3P

II2H3+

II2L3P

I2E+ & I3P

I2E & I3P

I2H

Type of gas

Pressure in mbar

G20

20

20

20

-

20

20

20

G25

25

-

-

25

25

20

-

G31

37

37

37

30

37

50

-

Burner

G350

Natural Gas G20 (20mbar) 34.02 MJ/m

3

(15°C-1013)

Gas Flow (15 C-1013 mbar)

(m

3

/h)

Nominal rate

8.1

Reduced rate

8.13

Heating Capacity

(kW)

Nominal rate

69.3

Reduced rate

69.1

Heating Rate

(kW)

Nominal rate

77

Reduced rate

76.8

Efficiency

%

Nominal rate

90

Reduced rate

90

Smoke analysis

G20 - 20mbar
@ 400V-3-50Hz

CO %

< 0.001%

Nox ppm

9 ppm

CO

2

%

9.7%

G350

YK* 155-175-200-225

1

Burner

G350

Natural Gas G25 (20 ou 25 mbar) 29.30 MJ/m

3

(15°C-1013)

Gas Flow (15 C-1013 mbar)

(m

3

/h)

Nominal rate

8.8

Reduced rate

8.21

Heating Capacity

(kW)

Nominal rate

62.9

Reduced rate

59.5

Heating Rate

(kW)

Nominal rate

71.5

Reduced rate

66.8

Efficiency

%

Nominal rate

88

Reduced rate

89

Smoke analysis

G25 - 25mbar
@ 400V-3-50Hz

CO %

< 0.001%

Nox ppm

-

CO

2

%

7.4%

Burner

G350

Propane Gas G31 (30, 37ou 50 mbar) 88.00 MJ/m

3

(15 C-1013)

Gas Flow (15 C-1013 mbar)

(m

3

/h)

Nominal rate

2.7

Reduced rate

2.56

Gas Flow (15 C-1013 mbar)

(kg/h)

Nominal rate

5.1

Reduced rate

4.9

Heating Capacity

(kW)

Nominal rate

57.5

Reduced rate

55.3

Heating Rate

(kW)

Nominal rate

65.3

Reduced rate

62.6

Efficiency

%

Nominal rate

88

Reduced rate

88.3

Combustion Air Flow
(Avec E=25%)

(m

3

/h)

Nominal rate

98

Reduced rate

93

Smoke analysis

G31 - 37mbar
@ 400V-3-50Hz

CO %

< 0.001%

Nox ppm

-

CO

2

%

8.9%