Installation – Trane RT-SVX19A-E4 User Manual

Page 30

Advertising
background image

Installation

RT-SVX19A-E4

30

Table 26 - Electrical data - YKD/YKH Supply fan motor

(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available

Table 27 - Electrical data - WKD/WKH Supply fan motor

(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available

Table 28 - Electrical data - Combustion Blower Motorr

YKD/H

YKD/H

YKD/H

YKD/H

155

175

200

250

Gas burner

Heating Models

G350

G350

G350

G350

Heating Input (G20)

(kW)

77

77

77

77

Heating Output

(kW)

69.3

69.3

69.3

69.3

Steady State Efficiency

(%)

90

90

90

90

No. Burners

1

1

1

1

No. Stages

2

2

2

2

Gas Connection Pipe Size

3/4" NPT

3/4" NPT

3/4" NPT

3/4" NPT

WKD/H

WKD/H

WKD/H

125

155

200

Indoor Fan

Nominal Airflow

(m

3

/h)

7140

8500

11210

Static pressure available (4)

(Pa)

200

175

200

Maximum static pressure available (5)

(Pa)

425

325

350

Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

Diameter / Width

(in / in)

15" / 15"

15" / 15"

18" / 18"

Drive type

Belt

Belt

Belt

Number

#

1

1

1

Motor HP (Standard/Oversized)

(kW)

2.2 / 3.0

2.2 / 3.0

3.0 / 4.6

Motor Rated Amps (Standard/Oversized)

(A)

4.6 / 6.5

4.6 / 6.5

6.5 / 9.0

Motor Locked rotor Amps (Standard/Oversized)

(A)

36.4 / 57

36.4 / 57

57 / 71.9

Motor RPM (Standard/Oversized)

(rpm)

1450 / 2870

1450 / 2870

2870 / 2900

TKD/H

TKD/H

TKD/H

TKD/H

155

175

200

250

Indoor Fan

Nominal Airflow

(m

3

/h)

8500

9850

11210

14100

Static pressure available (4)

(Pa)

175

250

200

125

Maximum static pressure available (5)

(Pa)

325

400

375

350

Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

Diameter / Width

(in / in)

15" / 15"

15" / 15"

18" / 18"

18" / 18"

Drive type

Belt

Belt

Belt

Belt

Number

#

1

1

1

1

Motor HP (Standard/Oversized)

(kW)

2.2 / 3.0

3.0 / 4.6

3.0 / 4.6

4.6 / -

Motor Rated Amps (Standard/Oversized)

(A)

4.6 / 6.5

6.5 / 9.0

6.5 / 9.0

9 / -

Motor Locked rotor Amps (Standard/Oversized) (A)

36.4 / 57

57 / 71.9

57 / 71.9

71.9 / -

Motor RPM (Standard/Oversized)

(rpm)

1450 / 2870

2870 / 2900

2870 / 2900

2900 / -

Advertising