Installation – Trane RT-SVX19A-E4 User Manual

Page 16

Advertising
background image

Installation

RT-SVX19A-E4

16

To increase airflow

Loosen variable sheave set screw
and turn sheave clockwise.

To decrease airflow

Loosen variable sheave set screw
and turn sheave counter-clockwise.

To increase belt tension

Loosen the nut (next to the idler
sheave) that secures the sheave in
place. With a wrench, apply
pressure clockwise on the outside
nut (round headed one), until
tension desired is reached. While
holding pressure with the tension
nut, retighten the nut next to the
idler sheave.

Figure 9 - Typical fan, motor, and sheave
assembly

A = Fan Housing
B = Terminal Block
C = Fan Sheave
D = Plastic Bushing
E = Belt Tension Adjustment Bolt
F = Idler Pulley

Table 6b - Belt tensioning

TK* / YK* /

WK*

Motor kW

Fan pulley

Type /

diam. (mm)

Fan pulley

Type /

diam. (mm)

Belt type

/ lengh (mm)

Belt

deflexion

(mm)

Deflexion

effort

mini kg

Deflexion

effort

maxi kg

Belt tension

mini

N

Belt tension

maxi

N

125

1,5

BK90 / 222

1VP44 / 105

BX68 / 1727

5,89

2,4

2,9

400

500

155

1,5

BK85 / 210

1VP44 / 105

BX68 / 1727

6

2,4

2,9

400

500

175

3

BK130 / 324

1VP44 / 105

BX75 / 1905

6,05

2,4

2,9

400

500

200

3

BK160 / 400

1VL40 / 95

BX90 / 2286

6,96

2,4

2,9

400

500

250

4,6

BK190 / 476

1VP50 / 121

BX96 / 2438

6,91

2,4

2,9

400

500

125

3

BK130 / 324

1VP44 / 105

BX75 / 1905

5,85

2,4

2,9

400

500

155

3

BK140 / 349

1VP44 / 105

BX77 / 1955

6,17

2,4

2,9

400

500

175

4,6

BK140 / 349

1VP56 / 136

BX75 / 1905

5,45

2,4

2,9

400

500

200

4,6

BK190 / 476

1VP56 / 136

BX96 / 2438

6,87

2,4

2,9

400

500

250

4,6

BK190 / 476

1VP56 / 136

BX96 / 2438

6,32

2,4

2,9

400

500

Advertising