Sensors, Controls – Trane RT-SVX19A-E4 User Manual

Page 33

Advertising
background image

Controls

33

RT-SVX19A-E4

CO

2

sensors

Wall-mounted and duct-mounted
CO

2

sensors

Table 30 - Specifications

WaII-mounted

Duct-mounted

Measuring range CO

2

0-200 ppm

Accuracy at 25°C

<+/- [40 ppm CO

2

+

3%

of reading]

(included repeatability

and calibration

uncertainty)

<+/- [30 ppm CO

2

+ 2%

of reading]

(included

repeatability and

caiibration

uncertainty)

Non-linearity

<1.0% full scale

Ternperature dependence
of output

0.3% full scale/°C

Long-term stability

<5.0% fulI scale /

5 years

Recomrnended
calibration interval

5 years

Response time

1 minute (0-63%)

Operating temperature

15-35°C

- 5-45°C

Storage temperature

-20-70°C

Humidity range

0-85% relative

humidity

Airflow range

0-10 m/s)

Output signals (jumper
selectable)

0-10Vdc

Resolution of anaIog
outputs

10 ppm CO2

Recomrnended external
load

Current output:

max 500

Voltage output:

min. 1000

Power supply

Nominal 24Vac

Power consumption

<5 VA

Warm-up time

<15 minutes

Dimensions (mm)

108 x 80 x 36

80 x 80 x 200

Advertising