Installing the Equipment

Page 2-6

Instruction Manual: evolution 5000 E57xx DSNG and DENG Voyager Encoder

ST.TM.E10076.3

The unit is designed for stationary or fixed use only. Ensure it is firmly and

safely located and has an adequate through-flow of air. Allow at least

50 mm free air-space at each side of the equipment. Units in racks can be

stacked without ventilation panels between. Racks containing stacked

equipment may need to be forced-air cooled to reduce the operating

ambient temperature. For stacking constraints contact Customer Services.
The 1U Encoder uses a similar air-flow path, with three fans on each side

of the unit. With both 1U and 2U units it is important not to block the front

air intake on the bottom-left corner of the front panel (see Figure 2.2).

Figure 2.2: Air Path Through the Enclosure

2

Warm air out

(right, front)

4

Warm air out

(left, rear)

1

Cool air in

(front – via bottom vent)

Do not block the air intake.

Two fans mounted

at front, right side

of unit

3

Cool air in

(right, rear)

Three fans mounted

at rear, left side of

unit