8.3.1 Connecting the EMD

The Environmental Monitoring Sensor (EMD) connects to any serial port on the Console Server via
a special EMD Adapter

and standard CAT5 cable. The EMD is powered over this serial connection

and communicates using a custom handshake protocol. It is not an RS232 device and should not
be connected without the adapter:

Plug the RJ plug on the EMD Adapter (model B090-EMD-
ADP) into RJ45 Port on the EMD (model B090-EMD).
Then connect the Console Server serial port to the RJ45
port of the EMD Adapter using the provided UTP cable.
If the 6 foot (2 meter) UTP cable provided with the EMD
is not long enough it can be replaced with a standard
Cat5 UTP cable up to 33 feet (10meters) in length (Tripp
Lite N002 series cables)

Screw the bare wires on any smoke detector, water

detector, vibration sensor, open-door sensor or general
purpose open/close status sensors into the terminals on
the EMD:

o B090-WLS

Console Server Water Leak Sensor

o B090-DCS

Console Server Door Contact Sensor

o B090-VS

Console Server Vibration Sensor

o B090-SD-110 Console Server Smoke Detector - 110V

o B090-SD-220 Console Server Smoke Detector - 220V

The EMD can be used only with a Console Server and cannot be connected to standard RS232
serial ports on other appliances.

Select Environmental as the Device Type in the Serial & Network: Serial Port menu for the port

to which the EMD is to be attached. No particular Common Settings are required.

Click Apply

Select the Serial & Network: Environmental menu. This will display all the EMD connections

that have already been configured