Serial Port Pattern Match Alert – This alert will be triggered if a regular expression is found in

the serial ports character stream that matches the regular expression you enter in the Pattern
field. This alert type will only be applied serial ports

UPS Power Status Alert - This alert will be triggered when the UPS power status changes

between On Line, On Battery, and Low Battery. This alert type will only be applied to UPS’s.

Environment and power alert - Refer to next section for details on selecting and configuring this

alert type

7.2.3 Configuring environment and power alert type

This alert type will be applied to any UPS’s, RPC’s and EMD temperature and humidity sensors you have
nominated.

Select Sensor Alert to activate

Specify which Sensor Type to alert on (Temperature, Humidity, Power Load and Battery

Charge)

Set the levels at which Critical and/or Warning alerts are to be sent. You can also specify

High and/or Low Set Points for sending alerts and the Hysteresis to be applied before
resetting off the alerts

Note

Specify the Set Point values are in:

Degrees Centigrade for Temperature
Amps (Current) for Power Load
% (Percentage) for Humidity and Battery Charge