3 Electrical connection

3.1 Connection instructions

Note the following instructions for electrical
connection:
- The connection must be made acc. to the

local installation standards (e.g. in Ger-
many acc. to the VDE-regulations).

- The wiring between VEGAMET and sensor

can be done with standard two-wire cable.

- If strong electromagnetic interference is

expected, screened cable is recom-
mended. The screening must be earthed
on both ends.

- The line resistances stated in the technical

data must not be exceeded.

- If overvoltages are expected, we recom-

mend a sensor electronics with integrated
overvoltage protection or the installation of
VEGA overvoltage arresters.

- The voltage supply of VEGAMET must

provide extra-low voltage to ensure pro-
tection class II. When using VEGASTAB
593, a reliable separation from the mains
circuits acc. to DIN VDE 0106, part 101 is
ensured.

2

28

24

22

30

32

d b z

+

+

+

+

+

+

+

+

L (+)
N (–)

6

10

12

2

3

+

+

1

20

16

18

+

+

+

+

Note:

Terminals d30 and z30 or d32 and z32 are
switched in parallel in the signal conditioning
instrument.

3.2 Wiring plan

Supply
voltage

Fail safe relay

Level relay 1

Sensor 1

Sensor 2

DISBUS output

Current outputs 1 … 3

Voltage outputs 1 … 3

Correction signal
Input 4

Correction signal
Input 5

Level relay 2