6 monitoring – VEGA VEGAMET 515V User Manual

Page 27

Advertising
background image

VEGAMET 515V

27

6.6 Monitoring

To activate the monitoring, the following
prerequirements must be met:

Meas.
value 50 %

High 5 %

Low –5 %

>55 %

Relay
deenergises

<45%

Configuration

• Choose in the menu item "

Input from

“ (un-

der the menu item "

Monitoring

“) input 4.

• Connect a key switch (opener) to input 4.

Confi-
gura-
tion

Config
inputs

Config
meas.
loop

TAG 1
Level

Appli-
cation

Level

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

Moni-
toring

Input
from

Input
no.4

• Choose in the menu range "

Parameter

adjustment relay outputs

“ in the menu item

"

Mode

“ the mode "

Monitoring

“ for the se-

lected relay.

The selected relay becomes energised. By
pushing the key switch (opener opens) the
actual measured value is first of all frozen
and, derived from this, the relay deenergises
if this value is underrun (Low) or exceeded
(High). After a reset and repeated push of
the key switch, the actual measured value is
again frozen.

Param.
TAG-
No. 1

TAG -
No. 1
%
xx,x

Adjust-
ment

Signal
condit-
ioning

Out-
puts

Curr.
out-
puts

Volt
outputs

Relay
outputs

Relay
output
1

prop.
to

Per-
cent

Unit

0,0%

Mode

(moni-
toring)

Low

%

5,0

High

%

5,0

Monit.
to

Low &
High

If the monitoring function has to be deacti-
vated, monitoring must first be cancelled in
the menu item "

Mode

“. Then the allocation of

the correction input (input 4) must be can-
celled under the menu item "

Monitoring

“.

Advertising