4 scaling, Parameter adjustment – VEGA VEGAMET 515V User Manual

Page 36

Advertising
background image

36

VEGAMET 515V

Set the number 1500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 0 % (if
you want to have a lower resolution of

the meas. value indication, you can also set
150 or 15).

Set the number 4500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 100 %.

Adjust the decimal point as shown
(with keys [+], [–] and [OK]).

Choose the term "Height“ in this
menu item (with keys [+], [–] and
[OK]).

If you have chosen "Height“ in the
previous menu item, you get a
choice of several units (mm, dm, cm,
m, yard…). Choose m (with the keys
[+], [–] and [OK]).

The scaled value is now shown in the
meas. value indication.

TAG -
No. 1

m

2,341

100 %

0 %

h=1.5 m

h=4.5 m

7.4 Scaling

The adjustments under scaling determine
which number values and which unit will actu-
ally be displayed on the measured value
indication (upper menu item). In the menu
items "0 % corresponds…“ and "100 % cor-
responds…“ you can enter with [+] or [–]
and [OK] values which should be displayed
at 0 % and at 100 % filling. In the menu item
"Decimal point…“ you determine the position
of the decimal point. In the next menu item
"prop. to…“ you get a choice of parameters:
push [+] or [–] to select percent, mass, vol-
ume, pressure etc. and save with [OK]. The
menu item "Unit…“ then serves up a corre-
sponding new choice, e.g. m, dm, cm, mm,
ft, yd and in, if you have selected the param-
eter "Height“ (compare chapter "8 Measuring
results and units“).

After a scaling, the requested output can be
assigned to the scaled value in the menu
range "Parameter adjustment outputs“ (menu
items "prop. to…“ and "Unit…“).

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Sig-
nal
condi-
tioning

Scal-
ing

Unit

– –

prop.
to

unde
fined

Deci-
mal
point

888,8

100%
corres
ponds

1000

0%
corres
ponds

0

Meas.
value
indication

Scaling example

You have a raised tank and you want the
level to be indicated in meters with three
places after the decimal point.

0%
corres
ponds

1500

100%
corres
ponds

4500

Deci-
mal
point

8,888

2.341 m

Percent
Pressure
Mass

prop.
to

Height

Unit

m

dm
cm
….

Parameter adjustment