In the menu item "

prop. to“, you can choose

between percent and volume. "Prop. to vol-
ume“ is then useful when you have chosen
spherical tank or user programmable curve
under "Conditioning - Linearisation curves“.
The output current or the output voltage then
assumes a value proportional to the volume
of the tank contents.

Unit:

Selection list dependent on the choice in the
previous menu item "prop. to“ (see chapter "8
Measuring results and units“).

The menu item range

"0%…100%“ only ap-

pears with measurement loop TAG-No. 3
(with gauge difference, level difference
measurement). The measured value can be
here -100 %.

Therefore, the range can be adjusted to
"

-100 % to +100 %“. The correlation between

output current and output voltage can be
seen in the diagram below.

Parameter adjustment

Volt output/Current output:

If "free“ is chosen, the following (light grey)
menu items appear:
- Volt at 0 %/100 %:

Individual voltage values between 0 V and
+10 V can be set.

- Current at 0 %/100 %:

Individual current values between 0 mA
and +20 mA can be set.

In failure mode:

The height of the output current/output volt-
age in case of failure is set here. If "--“ is
chosen, the existing value is maintained.

Volt limitation/Current limitation on:

Voltage or current of the output remain within
the values which were set in the menu item
Voltage output/Current output, even if a level
of more than 100 % or less than 0 % is meas-
ured.

Range

0%
+100%

Range

-100%
+100%

+100%

0%

-100%

4mA
0V

20mA
10V

+100%

0%

-100%

4mA
0V

20mA
10V