7 parameter adjustment, 1 adjustment with medium – VEGA VEGAMET 515V User Manual

Page 32

Advertising
background image

32

VEGAMET 515V

Parameter adjustment

7 Parameter adjustment

7.1 Adjustment with medium

You can either carry out the adjustment

with

medium or

without

medium. To carry out an

adjustment with medium, it is necessary that
you know the percentage values of the ves-
sel for the actual filling.

For this procedure, percentage values must
be entered for min. and max. values that
correspond to the actual fillings. The se-
quence of the min. or max. value is not impor-
tant. For example, if you know that your filling
is presently 80 %, you can enter in the menu
item Max. adjustment the value "80“. Then if
your filling is, for example, 10 %, you enter in
the menu item Min. adjustment the value "10“.

The larger the difference between the two
adjustment points, the more exact the meas-
urement over the whole measuring curve. It
would be ideal if the adjustment could be
carried out at 0 % and 100 %. For practical
reasons, however, it is not always possible to
completely fill or empty a vessel. The dis-
tance between the two adjustment points
however, should be at least 10 % of the sen-
sor range.

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

with
medium

Min-
adjust
at %

0,0

Max-
adjust
at %

100,0

Adjustment example

You know that your vessel is pres-
ently filled up to 80%. Move to the
menu item "Max-adjust at % 100.0“.

Briefly push the [–] key, so that the

figure 100.0 flashes (editing mode).

Continue pushing [–] until the figure
80.0 appears on the display. Now
push [OK] to save the adjustment.

Then, if your filling is for example
10 %, move to the menu item "Min-
adjust at % 0.0“. Briefly push the [+]
key until the figure 0,0 flashes (edit-

ing mode).

Continue pushing [+] until "10“ ap-
pears on the display. Now push [OK]
to save the adjustment.

Of course, you can carry out the adjustment
with medium also at 0 % and 100 % filling.
Please note: The figures 0 % and 100 % must
flash (editing mode) before they can be
saved with the [OK] key.

Note:

If the medium is later changed (medium with
another density value or dielectric constant)
and no new adjustment is possible or when
the MET indication and the DIS outputs refer
to height in metres, note the following: For
applications with hydrostatic pressure trans-
mitters, the adjusted density value must
correspond to the value of the medium.

The menu item "Density…“ is displayed if the
appropriate sensor type was selected under
"Configuration measurement loop“.

Max-
adjust
at %

100,0

Max-
adjust
at %

80,0

Min-
adjust
at %

0,0

Min-
adjust
at %

10,0

Lin.
curve

linear

Integr
ation
time s

0

Density
in
kg/dm3

1.000

Signal
condit-
ioning

Scaling

Advertising