26

VEGAMET 515V

Configuration

0

40

100%

40

100%

Meas. values in %

Taster

tared course

actual course

actual measured values

tared measured values

6.5 Tare

With the function "Tare“, a measured value
beginning at 0 % is created from the actual
measured value. The tare function can be
started via a key connected to correction
signal input 4.

The following steps are necessary to activate
the tare function:

• Connect a key (closer) to input 4.

• Choose in the menu item "

Input from

“ (un-

der the menu item "

Tare

“) input 4.

• Assign the tared value in the menu item

"

Unit

“ to the requested output (e.g. current,

volt, DIS, PC/DCS output, MET indication).

If you want to deactivate the tare function,
you first have to cancel taring in the menu
item "

Unit

“. Then you have to cancel the allo-

cation of the correction input (input 4) under
the menu item "

Tare

“.

Confi-
gura-
tion

Config
inputs

Config
meas.
loop

TAG 1
Level

Appli-
cation

Level

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

Tare

Input
from

Input
no.4

Param.
TAG-
No. 1

Adjust-
ment

Signal
condit-
ioning

Out-
puts

Curr.
out-
puts

Volt
out-
puts

Volt
output
1

prop.
to

Per-
cent

Unit

Tare
%

TAG -
No. 1
%
xx,x

Volume

Tare
V%