14

5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

5 Setup - Sensors up to software 3.99

5.1 Common adjustment menu for all signal

outputs

Through the parameter adjustment the instrument is adapted to the

application conditions. The parameter adjustment is carried out via an

adjustment menu.
Information:

In this operating instructions, all general parameters are described.

Additional instrument-specific parameters are described in the oper-

ating instructions of the respective sensor.

The following presentations are available in the measured value

display:

Level as digital value, sensor TAG

Level as digital value and bar graph, sensor TAG

Only with pressure transmitters: Level or pressure as digital value,

temperature value

With [->] you select different presentations of the measured value.

From each of these presentations, you can reach with [OK] the menu

overview. With [ESC] you move from the menu overview again to the

measured value indication.

The main menu is divided into five sections with the following func-

tions:

Basic adjustment
Display
Diagnostics
Service
Info

To damp process-dependent measured value fluctuations, set an

integration time of 0 … 999 s in this menu item.
Depending on the sensor type, the factory setting is 0 s or 1 s.

Damping

0 s

In this menu item you select the linearization curve:

Linear

Horizontal cylindrical tank

Spherical tank

User programmable

User programmable means: Switching on a linearization curve pro-

grammed via PC and PACTware
A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e. g. horizontal cylindri-

Measured value indica-

tion

Main menu

Basic adjustment/Damp-

ing

Basic adjustment/Lineari-

zation curve