6 Setup - radar sensors from software 4.0.0

PLICSCOM •

36433-EN-130228

are carried out. In this menu item, the value fir the function block is

selected:

PV (Primary Value):

– Linearised percentage value

SV1 (Secondary Value 1):

– Percent with radar, guided microwave and ultrasonic sensors

– Pressure or height with pressure transmitters

SV2 (Secondary Value 2):

– Distance with radar, guided microwave and ultrasonic sensors

– Percent with pressure transmitters

Height

Additional scalings (Out-Scale) are carried out within the function

block. In this menu item, the scaling unit is selected. For a better

overview, the units are combined in groups:

Additional scalings (Out-Scale) are carried out within the function

block. In this menu item, the unit of the scaling is entered.

To damp process-dependent measured value fluctuations, set an

integration time of 0 … 999 s in this menu item.
Depending on the sensor type, the factory setting is 0 s or 1 s.

Setup/AI FB1 Scaling unit

Setup/AI FB1 Scaling

Setup/AI FB1 damping