5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

The following values can be displayed:

Height

Pressure (only with pressure transmitters)

Distance (only with radar, guided microwave, ultrasonics)

Current

Scaled

Percent

Lin. percent

Temperature (only with pressure transmitters).

The selection "scaled" opens the menu items "Display unit" and

"Scaling". In "Display unit" there are the following options:

Height

Ground

Flow

Volume

Without unit

Depending on selection, the different units are in turn available.
In the menu item "Scaling", the requested numerical value with deci-

mal point is entered for 0 % and 100 % of the measured value.
There is the following relationship between the indication value in the

menu "Display" and the adjustment unit in the menu "Device settings":

With radar, guided microwave and ultrasonics, the displayed value

"Distance" means: presentation of the measured value in the

selected adjustment unit, e.g. m(d)

With pressure, the displayed value "Pressure" or "Height" means:

presentation of the measured value in the selected adjustment

unit, e.g. bar or m.

Displayed value

Scaled

Display unit

Volume

l

Scaling

0 % = 0.0 l
100 % = 100.0 l

In the menu item "Current output" you determine the behaviour of the

current output during operation and in case of failure. The following

options are available:

Service/Current output