VEGA PLICSCOM User Manual

Page 29

Advertising
background image

29

6 Setup - radar sensors from software 4.0.0

PLICSCOM •

36433-EN-130228

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e. g. horizontal cylindri-

cal or spherical tanks - and the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and the vessel volume. The linearization applies to the

measured value indication and the current output. By activating the

appropriate curve, the volume percentage of the vessel is correctly

displayed. If the volume should not be displayed in percent but e.g. in l

or kg, a scaling can be also set in the menu item "Display".

Caution:

Note the following, if the respective sensor is used as part of an over-

fill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

linearly proportional to the level. This must be taken into consideration

by the user, particularly when setting the switching point on the limit

signal indicator.

Entering a 4-digit PIN protects the sensor data against unauthorized

access and unintentional modification. In this menu item, the PIN is

displayed or edited and changed. However, this menu item is only

available if adjustment is enabled in the menu "Setup".

In delivery status, the PIN is "0000".

Additional adjustments/

Linearization

Additional adjustments/

PIN