3 adjustment menu profibus pa – VEGA PLICSCOM User Manual

Page 23

Advertising
background image

23

5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

HART mode

Standard
Address 0

The default setting is standard with address 0.

5.3 Adjustment menu Profibus PA

Level and pressure sensors operate as slaves on the Profibus PA. To

be identified as a bus participant, each sensor must have a unique

address. Each instrument is delivered with address 126. With this

address, it can at first be connected to an existing bus. However, the

address must be changed. This can be done in this menu item.

Sensor address

126

The channel is the input selector switch for function block (FB) of

the sensor. Within the function block, additional scalings (Out-Scale)

are carried out. In this menu item, the value fir the function block is

selected:

SV1 (Secondary Value 1):

– Percent with radar, guided microwave and ultrasonic sensors

– Pressure or height with pressure transmitters

SV2 (Secondary Value 2):

– Distance with radar, guided microwave and ultrasonic sensors

– Percent with pressure transmitters

PV (Primary Value):

– Linearised percentage value

Channel

PV lin. value

Radar, guided microwave and ultrasonic sensors deliver the following

measured values:

SV1 (Secondary Value 1): Percentage value after the adjustment

SV2 (Secondary Value 2): Distance value before the adjustment

PV (Primary Value): Linearised percentage value

PA-Out (value after passing the function block): PA output

A pressure transmitter delivers the following measured values:

SV1 (Secondary Value 1): Pressure or height value before adjust-

ment

SV2 (Secondary Value 2): Percentage value after the adjustment

PV (Primary Value): Linearised percentage value

Basic adjustment/Sensor

address

Channel

Display/Display

7)

The 4 … 20 mA signal of the HART sensor is switched off.The sensor

consumes a constant current of 4 mA. The measuring signal is transmitted

exclusively as digital HART signal.