5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

PA-Out (value after passing the function block): PA output

Temperature

In the menu item "Display" you can define which value should be

indicated on the display.

Displayed value

PA-Out

Profibus transmits two values cyclically. The first value is determined

in the menu item "Channel". The selection of the additional cyclical

value is made in the menu item "Additional PA value".
The following values are available with radar, guided microwave and

ultrasonic sensors:

SV1 (Secondary Value 1): Percentage value after the adjustment

SV2 (Secondary Value 2): Distance value before the adjustment

PV (Primary Value): Linearised percentage value

With pressure transmitters the following values are available:

SV1 (Secondary Value 1): Pressure or height value before adjust-

ment

SV2 (Secondary Value 2): Percentage value after the adjustment

PV (Primary Value): Linearised percentage value

Additional PA value

Here, you determine the unit and scaling for PA-Out. These settings

also apply to the values displayed on the display and adjustment

module if in the menu item "Displayed value" PA-Out was selected.
The following displayed values are available in "Out-Scale unit":

Pressure (only with pressure transmitters)

Height

Ground

Flow

Volume

Others (no unit, %, mA)

In the menu item "PV-Out-Scale", the requested numerical value with

decimal point is entered for 0 % and 100 % of the measured value.

Out-Scale-Unit

Service/Additional PA

value

Service/Determine Out-

Scale