20

5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

In this menu item, the PIN is activated/deactivated permanently.

Entering a 4-digit PIN protects the sensor data against unauthorized

access and unintentional modifications. If the PIN is activated perma-

nently, it can be deactivated temporarily (i.e. for approx. 60 min.) in

any menu item. The instrument is delivered with the PIN set to 0000.

PIN

Disable permanently?

Only the following functions are permitted with activated PIN:

Select menu items and show data

Read data from the sensor into the display and adjustment mod-

ule.

In this menu item the most important sensor information can be

displayed:

Instrument type

Serial number: 8-digit number, e.g. 12345678

Instrument type

Serial number
12345678

Date of manufacture: Date of the factory calibration

Software version: Edition of the sensor software

Calibration date

Software version

Date of last change using PC: Date of the last change of sensor

parameters via PC

Last change using PC

Sensor details, e.g. approval, process fitting, seal, measuring cell,

measuring range, electronics, housing, cable entry, plug, cable

length etc.

Sensor characteristics

Display now?

5.2 Adjustment menu 4 … 20 mA/HART

In the menu item "Display" you can define how the measured value

should be presented on the display.

Service/PIN

Info/Info

Display/Display