VEGA PLICSCOM User Manual
Page 35
35
6 Setup - radar sensors from software 4.0.0
PLICSCOM •
36433-EN-130228
In the menu item "Display" you can define which measured value
should be presented on the display.
The sensor delivers the following measured values:
•
PV (Primary Value): Linearised percentage value
•
SV1 (Secondary Value 1): Percentage value after the adjustment
•
SV2 (Secondary Value 2): Distance value before the adjustment
•
AI FB1 (OUT)
•
AI FB2 (OUT)
•
AI FB3 (OUT)
•
Height
In this menu item you simulate measured values via the signal output.
Hence, the signal path can be tested via the segment coupler up to
the input card of the control system.
How to start the simulation:
1. Push
[OK]
2. Select the requested simulation variable with [->] and confirm
with [OK].
3. With
[OK] you start the simulation, first of all the actual measured
value is displayed in %
4. Start the editing mode with [OK]
Display/Displayed value
Diagnosis/Simulation