6 Setup - radar sensors from software 4.0.0
PLICSCOM •
36433-EN-130228
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
In this menu item you can define the indication of the measured value
on the display.
The default setting for the indication value is e.g. distance with radar
sensors.
In this menu item you can define the scaling unit of the measured
value on the display.
In the menu item "Scaling", the requested numerical value with deci-
mal point is entered for 0 % and 100 % of the measured value.
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. via downstream
indicating instruments or the input card of the control system.
Setup/Current output
Min./Max.
Display/Displayed value
Display/Scaling size
Display/Scaling
Diagnosis/Simulation