6 Setup - radar sensors from software 4.0.0

PLICSCOM •

36433-EN-130228

In the menu item "Current output Min./Max.", you determine the reac-

tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

In this menu item you can define the indication of the measured value

on the display.

The default setting for the indication value is e.g. distance with radar

sensors.

In this menu item you can define the scaling unit of the measured

value on the display.

In the menu item "Scaling", the requested numerical value with deci-

mal point is entered for 0 % and 100 % of the measured value.

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. via downstream

indicating instruments or the input card of the control system.

Setup/Current output

Min./Max.

Display/Displayed value

Display/Scaling size

Display/Scaling

Diagnosis/Simulation