2 adjustment menu 4 … 20 ma/hart – VEGA PLICSCOM User Manual

Page 31

Advertising
background image

31

6 Setup - radar sensors from software 4.0.0

PLICSCOM •

36433-EN-130228

In this menu item, the hardware and software version of the sensor is

displayed.

In this menu item, the date of factory calibration of the sensor as well

as the date of the last change of sensor parameters are displayed via

the display and adjustment module or via the PC.

In this menu item, the features of the sensor such as approval, pro-

cess fitting, seal, measuring range, electronics, housing and others

are displayed.

6.2 Adjustment menu 4 … 20 mA/HART

To damp process-dependent measured value fluctuations, set an

integration time of 0 … 999 s in this menu item.

Depending on the sensor type, the factory setting is 0 s or 1 s.

In the menu item "Current output mode" you determine the output

characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode

< 3.6 mA.

Info/Instrument version

Info/Calibration date

Instrument features

Setup/Damping

Setup - Current output

mode