5 measurement setup level – VEGA VEGADIF 65 Foundation Fieldbus User Manual
Page 23
23
4 Mounting
VEGADIF 65 • Foundation Fieldbus
36130-EN-130417
+
–
1
2
2
3
5
5
6
4
4
Fig. 19: Measurement setup, flow measurement in liquids
1 Orifice or impact pressure probe
2 Blocking valves
3 VEGADIF 65
4 Separator
5 Drain valves
6 3-fold valve block
4.5 Measurement setup level
1. Mount VEGADIF 65 below the lower measurement connection so
that the effective pressure lines are always filled with liquid
2. Minus side is open to the atmospheric pressure
3. When measuring liquids with solid content, the mounting of sepa-
rators and drain valves is useful to be able to avoid and remove
buildup.
+
p
atm
min.
p
atm
2
3
4
5
1
Fig. 20: Measurement setup, level measurement in the open vessel
1 VEGADIF 65
2 Minus side is open to the atmospheric pressure
3 Blocking valve
4 Separator
5 Drain valve
In open vessels with ef-
fective pressure line