11 Supplement

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

Measuring cells ≥ 500 mbar

Ʋ Turn down 1 : 1 to 15 : 1

±0.075 % of the set span + influence of the chemical

seal

Ʋ Turn down > 15 : 1

±(0.0015 % x TD + 0.053 %) of the set span + influence

of the chemical seal

Influence of the product or ambient temperature
Applies to instruments in basic version with digital signal output (HART, Profibus PA, Foundation

Fieldbus) as well as to instruments with analogue current output 4 … 20 mA. Specifications refer

to the set span. Turn down (TD) = nominal measuring range/set span.

Temperature range

Measuring range

Thermal changes of the zero sig-

nal and the output span relating

to the adjusted span

-10 … +60 °C (+14 … +140 °F)

10 mbar, 30 mbar

±(0.31 x TD + 0.06) %

100 mbar

±(0.18 x TD + 0.02) %

500 mbar, 3 bar

±(0.08 x TD + 0.05) %

16 bar

±(0.1 x TD + 0.1) %

16 bar

±(0.08 x TD + 0.05) %

-40 … +10 °C (-40 … +50 °F)
+60 … +85 °C (+140 … +185 °F)

10 mbar, 30 mbar

±(0.45 x TD + 0.1) %

100 mbar

±(0.3 x TD + 0.15) %

500 mbar, 3 bar

±(0.12 x TD + 0.1) %

16 bar

±(0.15 x TD + 0.2) %

40 bar

±(0.37 x TD + 0.1) %

Applies also to instruments with analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 59: Thermal change, current output

Influence of the system pressure on the zero point and span
316L, Alloy C276-, Alloy C276 gold-rhodium coated diaphragm