VEGA VEGADIF 65 Foundation Fieldbus User Manual

Page 62

Advertising
background image

62

8 Setup

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

+

A

B

6

7

3

2

4

1

5

+

II

I

III

III

IV

Fig. 55: Preferred measurement setup for closed vessels with steam overlay
I VEGADIF 65

II 3-fold valve block

III Separator

IV Condensate vessel

1, 5 Drain valves

2, 4 Inlet valves

3 Breather valve

6, 7 Vent valves on VEGADIF 65

A, B Blocking valves

Proceed as follows:
1. Fill the vessel to just above the lower tap
2. Fill measuring system with medium

Open valve A and B: Open block valves
Fill the minus effective pressure line on the height of the conden-

sation pot

3. Remove air from instrument:

Open valve 2 and 4: Discharge medium
Open valve 3: Equalisation plus and minus side
Briefly open valve 6 and 7, then close again: Fill the measuring

instrument completely with the medium and remove air

4. Put measurement loop into operation:

Close valve 3: Separate plus and minus side
Open valve 4: Connect minus side
Now:
Valve 3, 6 and 7 are closed
Valves 2, 4, A and B are open.

Measurement setup

for closed vessels with

steam overlay

Prepare the adjustment