8 mounting external housing – VEGA VEGADIF 65 Foundation Fieldbus User Manual

Page 31

Advertising
background image

31

4 Mounting

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

1. Mount chemical seal with capillaries on top or laterally on the

pipeline

2. In vacuum applications: Mount VEGADIF 65 below the measure-

ment loop

3. The ambient temperature should be the same for both capillaries

+

1

4

2

2

3

Fig. 32: Measurement setup, differential pressure measurement in gases,

vapours and liquids
1 Chemical seal with bolting

2 Capillaries

3 E.g. filter

4 VEGADIF 65

4.8 Mounting external housing

1. Mark the holes according to the following drilling template
2. Depending on the mounting surface, fasten the wall mounting

plate with 4 screws

90 mm (3.54")

R3,5 mm

(0.14")

3 mm

(0.12")

70 mm (2.76")

8 mm

(0.32")

93 mm (3.66"

)

110 mm (4.33"

)

Fig. 33: Drilling template - wall mounting plate