6 Adjustment with the display and adjustment module PLICSCOM

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

1. Edit the % value in the menu item "Min. adjustment" with [OK].

Min. adjustment
0.00 %
=
0.0000 bar
0.0000 bar

2. Set the requested value with [+] and [->].
3. Confirm with [OK] and edit the requested bar value.
4. Set the requested bar value with [+] and [->].
5. Confirm with [OK] and move to max. adjustment with [->].
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.
The min. adjustment is finished.

Proceed as follows:
1. Edit the % value in the menu item "Max. adjustment" with [OK].

100.00 %
=
0.5000 bar
0.0000 bar

Information:

If the instrument has not yet been adjusted, the displayed pressure for

100 % corresponds to the nominal measuring range of the sensor (in

the above example 500 mbar).
2. Set the requested value with [->] and [OK].
3. Confirm with [OK] and edit the requested mbar value.
4. Set the requested value with [+] and [->].
5. Confirm with [OK] and move to the menu overview with [ESC].
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.
The max. adjustment is finished.

For the min. adjustment with density, a filling of the vessel is not

necessary. The numeric examples are stated in chapter Mounting,

Measurement setup, Density and interface of this instructions manual.
Proceed as follows:
1. Edit the % value in the menu item "Min. adjustment" with [OK].

Min. adjustment
0.00 %
=
0.0000 bar
0.0000 bar

2. Set the requested value with [+] and [->], for example 100 %.
3. Confirm with [OK] and edit the requested bar value.
4. Set the requested bar value with [+] and [->], for example

29.4 mbar.

5. Confirm with [OK] and move to max. adjustment with [->].

Max. adjustment with

level

Min. adjustment with

density