VEGA VEGADIF 65 Foundation Fieldbus User Manual

Page 72

Advertising
background image

72

11 Supplement

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

Max. torque screws mounting strap

30 Nm

Max. torque screws socket external

housing

5 Nm (3.688 lbf ft)

Weight approx.

4.2 … 4.5 kg (9.26 … 9.92 lbs), depending on process

fitting

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Channel Numbers

Ʋ Channel 1

Primary value

Ʋ Channel 2

Secondary value 1

Ʋ Channel 3

Secondary value 2

Ʋ Channel 4

Temperature value

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Dynamic behaviour output
Run-up time

≤ 20 s

I

63 %

100 %

t

t

1

t

2

Fig. 58: Presentation of the dead time t

1

and the time constant t

2

Version, nominal measuring range

Dead time t

1

Time constant t

2

Basic version 10 bar and 30 bar

100 ms

250 ms

Basic version 100 mbar

100 ms

180 ms

Basic version 500 mbar

100 ms

180 ms

Basic version, 3 bar

100 ms

180 ms

Basic version 16 bar and 40 bar

100 ms

180 ms

Chemical seal version, all nominal measuring ranges

Dependent on the chemi-

cal seal

Dependent on the chemi-

cal seal

Bus response time with Foundation Fieldbus

Ʋ cyclically approx.

10 ms

Advertising