7 measurement setup differential pressure – VEGA VEGADIF 65 Foundation Fieldbus User Manual

Page 29

Advertising
background image

29

4 Mounting

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

1

+

0,3 m

0,8

1,0

Fig. 28: Measurement setup with interface measurement

4.7 Measurement setup differential pressure

Mount VEGADIF 65 above the measurement loop so that con-

densate can drain off in the process cable.

4

4

1

2

3

3

+

Fig. 29: Measurement setup with differential pressure measurement between

two pipelines in gases and vapours
1 VEGADIF 65

2 3-fold valve block

3 Blocking valves

4 Pipelines

Mount VEGADIF 65 below the measurement loop so that some

condensate can collect in the effective pressure lines.

The ventilation is carried out via the ventilation valves on the instru-

ment, the 5-fold valve block enables blowing out the cables.

In gases and vapours

In vapour and conden-

sate plants

Advertising