GE Industrial Solutions EntelliGuard G User Manual

Page 10

Advertising
background image

EntelliGuard® G Circuit Breaker

DEH-41304C

Section 2 – Product Specifications

13 March 14

10

©2012 General Electric All Rights Reserved

Table 2.4. EntelliGuard G Non-Automatic Circuit Breaker: ANSI Version*

Envelope

Type

Amps

Rated

Interrupting

Current

Rated Endurance

Minimum Mechanical

Endurance

Minimum Electrical

Endurance at 480 V

Minimum Electrical

Endurance at 600 V

1

S

800

42

12,500

10,000

7,500

1

N

800

42

12,500

10,000

7,500

1

N

1600

42

12,500

10,000

7,500

1

N

2000

42

12,500

7,500

5,000

2

M

3200

65

5,000

5,000

5,000

3

B

4000

100

5,000

3,000

2,000

3

B

5000

100

5,000

2,000

1,500


Table 2.5. EntelliGuard G Non-Automatic Circuit Breaker/Molded Case Switch: UL Version*

Envelope

Type

Amps

Short

Interrupting

Current (kA)

Rated Endurance

Minimum Mechanical

Endurance

Minimum Electrical

Endurance at 480 V

Minimum Electrical

Endurance at 600 V

1

S

800

42

12,500

10,000

7,500

1

S

1200

42

12,500

10,000

7,500

1

N

800

42

12,500

10,000

7,500

1

N

1600

42

12,500

10,000

7,500

1

N

2000

42

12,500

7,500

5,000

2

M

3000

65

5,000

5,000

5,000

3

B

4000

100

5,000

3,000

2,000

3

B

5000

100

5,000

3,000

1,500

3

B

6000

100

5,000

1,500

1,000

* GE internal quality testing requirements exceeded 20,000 mechanical and electrical operations.


Table 2.6. Key to Tables 2.2 through 2.5

Type Description

Type Description

E

Sq. Rated (ICW = ICU) 400 A to 2000 A, 85 kAIC at 480/508 V

H 85 kAIC at 480/508 V; 65 kAIC at 600/635 V

B Sq. Rated (ICW = ICU) 3200 A to 6000 A, 100 kAIC at 480/508 V

M 100 kAIC at 480/508 V; 85 kAIC at 600/635 V

N 65 kAIC at 480/508/600/635 V

L

150 kAIC at 480/508 V; 100 kAIC at 600/635 V

W 200 kAIC at 480/508 V; 100 kAIC at 600/635 V

Table 2.7. Agency Certification (All industry standards referenced in this table are the latest version at the time the
product is sold.)

Standard Number

Title

ANSI C37.13,16,17, 20, 50

Low-voltage AC Power Circuit Breakers

NEMA SG 3, 5

Low-voltage Power Circuit Breakers

NEMA AB1

UL 1008*

Automatic Transfer Switches

UL 1066

Low voltage AC and DC Power Circuit Breakers Used in Enclosures

UL 489

Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

CSA 22.2, No 5.1

Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

IEC 60947 Part 1

Low Voltage Switchgear and Control Gear - General Rules

IEC 60947 Part 2

Low Voltage Switchgear and Control Gear - Circuit-Breakers

IEC 60947 Part 5

Low Voltage Switchgear and Control Gear - Accessories

IEC 60947 Part 3

Low Voltage Switchgear and Control Gear - Switches, Disconnects, Switch-Disconnects and
Fuse-Combination Units

IEC Environmental: 68-2-1,-2,-3,-6,-11,-
14,-14,-27,-29,-30,-31

IEC Environmental: 721

GB14048

China standards and CCC Mark

ABS (American Bureau of Shipping

Germanischer Lloyds

CUL

Low-voltage AC Power Circuit Breakers

*Suitable for use in UL1008 applications.

Advertising