EntelliGuard® G Circuit Breaker

13 March 14

Section 6 – Accessories Description

©2012 General Electric All Rights Reserved

27

SECTION 6 – ACCESSORIES DESCRIPTION

WARNING

IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Ensure only qualified personnel install, operate, service
and maintain all electrical equipment.
Failure to comply with these instructions could
result in death or serious injury.


GENERAL INFORMATION

A wide range of optional accessories are interchangeable
across all EntelliGuard G power circuit breakers, regardless
of nominal rating or envelope/frame size. Each accessory
incorporates easy-fit design features for quick installation,
either at the factory or in the field (Fig. 6.1).

NOTE: Replacement accessories have an “R” at the end of
the catalog number as shown.

Figure 6.1. Accessory Mounting

INDIVIDUAL ACCESSORIES

Motorized Spring Charging Unit
The unique motor/gearbox unit is specially designed to
operate with the full range of EntelliGuard G. It is easily
fitted with three heavy-duty bolts. After a breaker close
operation, the unit automatically recharges the spring and
makes it ready for immediate open and re-close should the
need arise. High speed recharging ensures that the springs
are fully charged within approximately three seconds
following a release. All electrically operated (EO) ANSI/UL
breakers are equipped with “Spring Charged” contacts
(GSCC1R) for status indication (Table 6.1).

Table 6.1 Motor Operators

Envelope

Power

Consumption

Nominal Control

Voltage

IEC Range (85% to 110%)

ANSI Range

UL Range

(85% to 110%)

Cat No.

1

DC – 300 W

24 Vdc/30 Vdc

20.4 V to 26.4 V

-

20.4 V to 26.4 V

GM0124DR

48 Vdc

40.8 V to 52.87 V

38 V to 56 V

40.8 V to 52.87 V

GM01048DR

60 Vdc

51 V to 66 V

-

51 V to 66 V

GM01060DR

72 Vdc

61.2V to 79.2 V

-

61.2 V to 79.2 V

GM01072DR

110 Vdc/130 Vdc

106.25 V to 137.5 V

100 V to 140 V

106.25 V to 137.5 V

GM0113ODR

250 Vdc

212.5 V to 275 V

200 V to 280 V

212.5 V to 275 V

GM01250DR

AC – 350 VA

48 Vac

40.8 V to 52.87 V

-

40.8 V to 52.87 V

GM01048AR

120 Vac

102 V to 132 V

104 V to 127 V

102 V to 132 V

GM01120AR

240 Vac

204 V to 264 V

208 V to 254 V

204 V to 264 V

GM01240AR

277 Vac

235.5 V to 304.7 V

-

235.5 V to 304.7 V

GM01277AR

2 and 3

DC – 480 W

24 Vdc/30 Vdc

20.4 V to 26.4 V

-

20.4 V to 26.4 V

GM0224DR

48 Vdc

40.8 V to 52.87 V

38 V to 56 V

40.8 V to 52.87 V

GM02048DR

60 Vdc

51 V to 66 V

-

51 V to 66 V

GM02060DR

72 Vdc

61.2 V to 79.2 V

-

61.2 V to 79.2 V

GM02072DR

110 Vdc/130 Vdc

106.25 V to 137.5 V

100 V to 140 V

106.25 V to 137.5 V

GM0213ODR

250 Vdc

212.5 V to 275 V

200 V to 280 V

212.5 V to 275 V

GM02250DR

AC – 560 VA

48 Vac

40.8 V to 52.87 V

-

40.8 V to 52.87 V

GM02048AR

120 Vac

102 V to 132 V

104 V to 127V

102 V to 132 V

GM02120AR

240 Vac

204 V to 264 V

208 V to 254 V

204 V to 264 V

GM02240AR

27 Vac

235.5 V to 304.7 V

-

235.5 V to 304.7 V

GM02277AR

Spring charge contact is power rated only, as shown below.

AC Ratings

DC Ratings

Voltage

Amps

Voltage

Amps

110 V-130 V

AC21-15 A

24 V

DC21-15 A

AC23-10 A

110 V-130 V

DC21-10 A

220 V -240 V

AC21-10 A

250 V

DC21-5 A

AC23-5 A

-

-

Spring charge time = 3 sec max.

Recommended fuse amps: contact factory.

Duty cycle = 2/min.

Envelope 1 motors: running VA ~ 300 VA; inrush = 2 to 3 times.

Envelope 2 and 3 motors: running VA ~ 450 VA; inrush = 2 to 3 times.