EntelliGuard® G Circuit Breaker

13 March 14

Section 7 – Accessories Installation

©2012 General Electric All Rights Reserved

37

Figure 7.13. Cluster Views


Upper Cluster Contact Grounding
1. Using the cluster pliers, remove the upper cluster

contacts the rear of the circuit breaker.

2. Position the grounding bar on the exposed top of the

top terminals, ensuring the spring-loaded grounding
contact is facing left when viewed from the rear.

3. Install bolts and washers using the threads in the

grounding bar, one bolt per pole. Torque to 30 N m.

4. The spring loaded grounding contact will engage with

the top fixed grounded contact block in the cassette
when the breaker is racked to the CONNECTED position
(Fig 7.14).


Figure 7.14 Cluster Contact Grounding Top Location

Lower Cluster Contact Set Grounding (Figs. 7.15 and 7.16)
1. Using the cluster pliers, remove the lower cluster

contacts at the rear of the circuit breaker.

2. Position the grounding bar on the exposed top of the

bottom terminals, ensuring the spring-loaded grounding
contact is facing left when viewed from the rear

3. Install bolts and washers using the threads in the

grounding bar, one bolt per pole. Torque to 30 N m.

4. The spring loaded grounding contact will engage with

the bottom fixed grounded contact block in cassette
when the breaker is racked to the CONNECTED position.


Figure 7.15. Cluster Contact Grounding Top Location


Figure 7.16. Fixed Grounding Contact in Cassette


MECHANICAL TRIP ALARM INSTALLATION

1. Remove the front cover.
2. Remove the trip unit.
3. Install the mechanical trip alarm as shown in Fig. 7.17.

Figure 7.17. Mechanical Trip Alarm