DEH-41304C

EntelliGuard® G Circuit Breaker

13 March 14

Section 6 – Accessories Description

©2012 General Electric All Rights Reserved

29

Table 6.5. UVR Operating Characteristics

Power

Consumption

Nominal Control

Voltage

Catalog

Number

DC: 350 W,

20 W (sealed)

AC: 350 W

(inrush),

20 W (sealed)

24/30 Vdc

GUVT030DR

40 Vdc; 48 Vac/dc

GUVT048R

60 Vdc

GUVTO60DR

110/130/120 Vac

GUVT130R

208 Vac

GUVT208AR

220 Vdc/240 Vac

GUVT240R

250 Vdc/277 Vac

GUVT277R

Duty cycle = 2/min.

Inrush = 350 VA (ac), 350 W (dc).

Holding = 60 VA (ac), 50 W (dc).


Time Delay Module (TDM) for UVR (Externally Mounted)

The de-energized operation of the Under Voltage release can
be delayed. This optional, externally mounted module has an
adjustable time delay of 0 s to 3 s. The device can be
implemented to prevent undesired breaker tripping due to
momentary voltage interruptions and is connected in series
with the Under Voltage release. The time delay is in addition
to the time delay from the breaker mounted UVR accessory.
The time delay module starts counting at 50% of rated
voltage (Fig. 6.2 and Table 6.6).

Figure 6.2. Time Delay Module

Table 6.6 TDM Characteristics

Nominal Control Voltage

Catalog No.

48VDC

GTDM048D

48VAC

GTDM048A

60VDC

GTDM060D

120VDC

GTDM120D

120VAC

GTDM120A

208VAC

GTDM208A

240VDC

GTDM240D

240VAC

GTDM240A

250VDC

GTDM250D

277VAC

GTDM277A

Remote Operation Coil Combination
Each breaker accepts a maximum of four coils in the
combinations shown in Table 6.7. All coils are mounted from
the front and snap onto the mechanism after the fascia is
removed.

Table 6.7. Remote Operation Coil Combination

Combination

Coil Position on Fascia (from left)

1

2

3

4

1

-

shunt

CC

UV

2

shunt

shunt

CC

UV

3

shunt

UV

CC

UV


Auxiliary Switches
Auxiliary switches indicate breaker main contact position.
They change their state in the same time sequence as the
breaker main contacts. See Tables 6.8 and 6.9 for available
combinations and ratings.


Table 6.8. Auxiliary Switches

Contact Configuration

Cat. No.

Power rated (3NO+3NC)

GAUX3R

Power rated (3NO+3NC) + low signal (Hi-Fi)
(2NO+2NC)

GAUX5R

Power rated (8NO+8NC)

GAUX6R

Power rated (4NO+4NC) + low signal (Hi-Fi)
(4NO+4NC)

GAUX8R


Table 6.9. Auxiliary Switch Ratings and Secondary
Disconnect Points

Contact Configuration

Power

Rated

Hi-Fi

Cat. No.

Power rated

(3NO+3NC)

A14 - A25

N/A

GAUX3R

Power rated (3NO+3NC) +

low signal (Hi-Fi)

(2NO+2NC)

A14 - A25

B10 - B13,

B23 - B26

GAUX5R

Power rated

(8NO+8NC)*

A14 - A25,

B4 - B13,

B17 - B26

N/A

GAUX6R

Power rated (4NO+4NC) +

low signal (Hi-Fi)

(4NO+4NC)*

A14 - A25,

B12 - B13,

B25 - B26

B4 - B11,

B17 - B24

GAUX8R

*Options are not available for side mounted sec disc blocks.

High Fidelity refers to gold-plated contacts. Use for signal level outputs
(10 mA min to 100 mA max., 8 Vdc to 30 Vdc, 125 Vac.