EntelliGuard® G Circuit Breaker

DEH-41304C

Section 6 – Accessories Description

13 March 14

32

©2012 General Electric All Rights Reserved

Charging Spring Status Indicator
Factory-installed on the motor, this auxiliary switch
indicates that the circuit breaker is charged and is
standard with the spring-charging motor (Table 6.18).

Table 6.18. Spring Charged Contact (1 NO)

Ratings

Cat. No.

AC

120 Vac

6 A

GSCC1R

250 Vac

6 A

DC

125 Vac

0.5 A

250 Vac

0.25 A

Secondary Disconnects (Factory-installed/Field
Installable)
Inputs and outputs to the circuit breaker are wired
through secondary disconnects located on either the top
or the side (Envelope 1 only) of the breaker. The plug-style
secondary disconnects engage mating disconnects in the
breaker cubicle when the breaker is in the TEST or
CONNECT position. Up to 78 points are available so that
all breaker accessories can be wired to dedicated
disconnect points. See Table 6.19 for block location and
Table 6.20 for secondary disconnect parts.

Table. 6.19. Block Location

Top Disconnect

Block B

Block A

Si

de

D

is

con

nect

Bl

ock

A

circuit breaker/cradle
viewed from the front

Table. 6.20. Secondary Disconnect Parts

Breaker

Type

Mounting

Number of

Poles

Cat. No.

Fixed

top

39 pole set

GSDFTR1

side

top

78 pole set

GSDFTR2

78 pole set

GSDFSR

Drawout

side

78 pole set

GSDWTR

39 pole set

GSDWSR

Set contains both the male and female sides of the secondary
disconnect.

Drawout kits include the metal bracket for connections to the
cassette.

Breakers ordered with side mounted disconnects come standard
with 78 pole secondary disconnect.

Ground Fault
The EntelliGuard TU Trip Unit provides a non-core CT
input for zero sequence or residual summation current.
The expected ratio is 1A = 100%.

Neutral Rogowski CT’s

The Neutral Rogoswki CT’s are used to measure the
Neutral Current and is required when Internal Ground
Fault is selected on the trip unit. There are two types
available:

1. Encased with Terminal Screws: The Rogowski coil

is encased in a plastic mold with two terminal
screws. No additional mounting hardware is
required as the encasing is molded to the
mounting dimensions. Table 6.21

2. Loose Rogowski Coil with separate mounting

hardware: The coil and mounting hardware are
separate. The coil comes with the two wire leads
for connection to a terminal block. Table 6.21a

Table 6.21. Neutral Rogowski CTs

(Encased with Terminal Screws)

Envelope

Current Rating

Cat. No.

1

400 A

G04HNRCE

600/630 A

G07HNRCE

800 A

G08HNRCE

1000 A

G10HNRCE

1200/1250 A

G13HNRCE

1600 A

G16HNRCE

2000 A

G20HNRCE

2

400 A

G04MNRCE

600/630 A

G07MNRCE

800 A

G08MNRCE

1000

G10MNRCE

1200/1250 A

G13MNRCE

1600 A

G16MNRCE

2000 A

G20MNRCE

2500 A

G25MNRCE

3000/3200 A

G32HNRCE

4000 A

G40HNRCE

3

3000/3200 A (1600 A x 2)

G32GNRCE

4000 A (2000 A x 2)

G40MNRCE

5000 A (2000 A x 2)

G50MNRCE

6000/6400 A (3200 A x 2)

G04MNRCE