EntelliGuard® G Circuit Breaker

13 March 14

Section 6 – Accessories Description

©2012 General Electric All Rights Reserved

31

Table 6.15. Interlock Configurations

Typical Circuit

Interlock Configuration

Possible Combinations

Type A

1 from 2 way interlock

2 cable configuration

Interlocking between two circuit breakers

One normal power supply

One generator (emergency) supply

B1

B2

O

O

1

O

O

1

B1 can close only if B2 is open.
B2 can close only if B1 is open.

Type B

1 from 3 way interlock

6 cable configuration

Interlocking among three circuit breakers

Three power supplies (generator or transformers)

feeding the same busbar but parallel operation is

prevented.

Available on request.

B1

B2

B3

O

O

O

1

O

O

O

1

O

O

O

1

Only 1 of 3 breakers can be closed.

Type C

1 from 3 way interlock

6 cable configuration

Interlocking among three circuit breakers

Two bus sections can be powered by single

transformer (bus coupler closed) or both

transformers (bus coupler open).

Available on request.

B1

B2

B3

O

O

O

1

O

O

O

O

1

O

1

O

1

1

O

O

1

1

v

O

1

Any two from three breakers can be closed.

Any one from three breakers can be closed.

Two breakers must be closed to prevent the
third breaker from closing.

Type D

1 from 3 way interlock

6 cable configuration

Interlocking between three circuit breakers

Two normal power supplies not set in parallel.

One power supply may assist the priority circuit.

Available on request.

B1

B2

B3

O

O

O

1

O

O

O

O

1

1

O

1

O

1

O

B1 and/or B3 can be closed only if B2 is open.

B2 can only be closed if B1 and B2 are both
open.

Contact factory for availability

Bell Alarm with Lockout
The bell alarm provides remote indication that the circuit
breaker has opened because of an electrical fault. The
Lockout feature is integral to the trip unit. When a Bell
Alarm is supplied with the breaker, the trip unit dial is set
and locked to the manual position. In order to re-close
the breaker, the Lockout button must be pushed in/reset
on the trip unit 1-Form C contact (Tables 6.16 and 6.17).

Table 6.16. Bell Alarm Switches

Switch Configuration

Cat. No.

One single pole, double throw switch
(1-Form C contact)

GBAT1R


Table 6.17. Bell Alarm Ratings (Common NO/NC
Contact Configuration)

Ratings

AC

120 Vac

6 A

250 Vac

6 A

DC

125 Vac

0.5 A

250 Vac

0.25 A