GE Industrial Solutions EntelliGuard G User Manual

Page 26

Advertising
background image

EntelliGuard® G Circuit Breaker

DEH-41304C

Section 5 – Locks and Interlocks

13 March 14

26

©2012 General Electric All Rights Reserved

Horizontal Mounting (Fig. 5.16)
1. Measure distance ”A” from the right hand face of one

cassette to the right hand face of the other.

2. Ensure the minimum cable radius is not less than

125 mm. Cable length is “A” + 67 cm. Longer cables
may be used; however, they must be free from
obstruction and no longer than 3 m.


Figure 5.16: Horizontal Mounting Dimensions

Circuit

Breaker 1

Circuit

Breaker 2

“A”
cm

14 cm (Min.) Cable

SAFETY SHUTTERS INSTALLATION (Fig. 5.17)

1. Ensure circuit breaker is in the DISCONNECTED position

and the racking handle is removed.

2. Pull out the top or bottom shutter locking bar, or both

as required, to reveal the locking eye.

3. Hold while inserting padlock(s). (Shaft diameter is 6 mm

min. to 8 mm max.).

4. Apply the provided “BUSBAR” and “CIRCUIT” designation

labels.


Figure 5.17. Shutter Padlocking

A

A Shutter locking bar

Table 5.1. Fixed-Mounted Circuit Breaker Locking

Function

Number and Type of Padlocks/Locking Devices

Padlock Shaft Diameter

Padlock for “ON” pushbutton restricting access to
the button in raised position

maximum of one lock of may be mounted

3 mm to 9.5 mm

Padlock for “OFF” pushbutton restricting access
to the button in depressed state to block ON
operations

maximum of one lock of may be mounted

3 mm to 9.5 mm

Padlock for breaker trip free condition

maximum of three locks may be mounted

3 mm to 9.5 mm

Breaker Key Lock in OPEN position (Optional)

maximum of four key locks of any one type
(optional Kirk/Ronis/Profalux) may be used

maximum one of Castle lock may be installed

N/A


Table 5.2. Drawout Circuit Breaker Locking

Function

Number and Type of Padlocks/Locking Devices

Padlock Shaft Diameter

Racking mechanism screw access blocking
padlock in DISCONNECTED/TEST/CONNECTED
positions

three locks may be mounted in one slot

3 mm to 9.5 mm

Racking mechanism screw access blocking and
breaker trip free position key lock in
DISCONNECTED/TEST/CONNECTED positions
(Ronis/Profalux)

maximum of two locks

3 mm to 9.5 mm

Padlocking provisions on the drawout rails
prevent unauthorized installation of a breaker
that has been removed from the cassette for
equipment or load maintenance.

maximum of three padlocks

3 mm to 9.5 mm

Advertising