EntelliGuard® G Circuit Breaker

DEH-41304C

Section 6 – Accessories Description

13 March 14

28

©2012 General Electric All Rights Reserved

Circuit Breaker Closing Coils – Standard and Commanded
Two, easy-to-fit, clip-on closing coil options with simple,
plug-in connections are available. Both options offer
electrical remote release of the spring charged closing
mechanism. Both options include a standard anti-pump
safety feature ensuring that the remote signal must be
released before further close commands are allowed. The
Command Close Coil additionally provides for local
electrical command of the accessory and remote
command over communications via the EntelliGuard trip
unit (Table 6.2).

Table 6.2. Closing Coil Characteristics

Type

Power

Consumption

Nominal Control

Voltage

Catalog

Number

Closing

Coil

DC: 350 W,

20 W (sealed)

AC: 350 W

(inrush),

20 W (sealed)

24/30 Vdc

GCCN24DR

40 Vdc; 48 Vac/dc

GCCN048R

60Vdc

GCCNM060DR

70 to 72 Vac/Vdc

GCCN072R

110/130/120 Vac

GCCN120R

208 Vac

GCCN208AR

220 Vdc/240 Vac

GCCN240R

250 Vdc/277 Vac

GCCN277R

Command

Operated

Closing

Coil

DC: 350 W,

20 W (sealed)

AC: 350 W

(inrush),

20 W (sealed)

24/30 Vdc

GCCC24DR

40 Vdc; 48 Vac/dc

GCCC048R

60 Vdc

GCCCM060DR

70 to 72 Vac/Vdc

GCCC072R

110/130/120 Vac

GCCC120R

208 Vac

GCCC208AR

220 to 250 Vac/Vdc/249 Vac

GCCC240R

Duty cycle = 2/min.

Closing coil inrush = 350 VA.


Command Operation Module
This module energizes the closing coil to cause the breaker
to close whenever control power is applied to the
accessory and when commanded from the breaker trip
unit or breaker front panel push button (electrical closing).

Shunt Trip (ST)
Energizing the shunt trip, via local or remote input, will
instantaneously activate the circuit breaker mechanism,
ensuring a rapid open operation. The standard auxiliary switch
ensures automatic isolation whenever the circuit breaker is
open. The shunt trip release is a straightforward, field installable
accessory available in wide range of voltages (Table 6.3).

Table 6.3. Extended Range Shunt Trip for UL Ground Fault
and ANSI DC Rating Applications.

Nominal Control Voltage

Catalog Number

24 Vdc

GSTG024DR

48 Vac/dc

GSTG048R

70/72 Vdc

GSTG072DR

110 Vdc/120 Vac

GSTG120R

125 Vdc

GSTG125DR

208 Vac

GSTG208AR

240 Vac

GSTG240R

250 Vdc/277 Vac

GSTG277R

Pickup range = 55%-110%.

Duty cycle = 2/min.

Inrush = 480 A (ac), 480 W (dc).

Holding = 60 VA (ac), 50 W (dc).

Status Indication Switch (Coil Signaling Contact)
A plug-in module is available to provide status indication via
the secondary disconnects and trip unit. Coil Signaling
Contacts are available for closing coils, shunt trips and under
voltage releases, see Table 6.4. Contac t is mounted on top of
the Accessory Device.

Table 6.4 Coil Signaling Contact Module

Type and

Configuration

Rating

Cat. No.

1 Power rated +
1 Low signal (Hi-Fi)
(1NO contact each)

AC

120 Vac

6 A

GCSP1R

250 Vac

6 A

DC

125 Vac

0.5 A

250 Vdc

0.25 A

AC

125 Vac

0.1 A

DC

30 Vdc

0.1 A

2 Low signal (Hi-Fi)
(1NO contact each)

AC

125 Vac

0.1 A

GCSP2R


Under Voltage Release (UVR) With Fixed Time Delay

The UVR instantaneously activates the circuit breaker trip
mechanism when the source voltage drops below the low
voltage threshold. The UVR is also a simple, field installable
device. NOTE: This accessory acts as a permissive; it is a no-
voltage/no-close device. The circuit breaker cannot be closed
(manually or electrically) unless the under voltage release coil
is energized above the required threshold. The UVR shunt trip
with fixed time delay is specifically intended for applications
where a delay period (ride-through) is required due to
potential voltage events. The delays are 50 ms when system
voltage drops to 50% and 20 ms when system voltage drops
below 50%. See Table 6.4. (A Time Delay Module is also
available, see next page).