GE Industrial Solutions EntelliGuard G User Manual

Page 33

Advertising
background image

DEH-41304C

EntelliGuard® G Circuit Breaker

13 March 14

Section 6 – Accessories Description

©2012 General Electric All Rights Reserved

33

Table 6.21a. Neutral Rogowski CTs

(Loose Rogowski Coil and mounting hardware)

Envelope

Current Rating

Cat. No.

1

400 A

G04HNRC

600/630 A

G07HNRC

800 A

G08HNRC

1000 A

G10HNRC

1200/1250 A

G13HNRC

1600 A

G16HNRC

2000 A

G20HNRC

2

400 A

G04MNRC

600/630 A

G07MNRC

800 A

G08MNRC

1000

G10MNRC

1200/1250 A

G13MNRC

1600 A

G16MNRC

2000 A

G20MNRC

2500 A

G25MNRC

3000/3200 A

G32HNRC

4000 A

G40HNRC

3

3000/3200 A (1600 A x 2)

G32GNRC

4000 A (2000 A x 2)

G40MNRC

5000 A (2000 A x 2)

G50MNRC

6000/6400 A (3200 A x 2)

G04MNRC


Ready to Close Contact (Table 6.22)
This contact indicates that the following conditions are
met and the circuit breaker can be closed:

The circuit breaker is open.

The closing springs are charged.

The circuit breaker in not locked/interlocked in open
position.

There is no standing closing order.

There is no standing opening order.

Table 6.22. Ready to Close Contacts (1 NO)

Ratings

Cat. No.

AC

120 Vac

6 A

GRTC2R

250 Vac

6 A

GRTC2R

DC

125 Vac

0.5 A

GRTC1R

250 Vac

0.25 A

GRTC3R


Sealed Door Panel Escutcheon
An optional complete IP54 front door pane is available

when a higher degree of protection is needed.

Mechanical Operations Counter
Used with either manual or motor charged circuit
breakers, the counter provides an accurate record of the
cumulative number of complete breaker closing
operations (Table 6.23).

Table 6.23. Miscellaneous Accessories

Description

Cat. No.

IP54 Door Panel - Withdrawable Type

GF54D

IP54 Door Panel - Fixed Pattern

GW54D

Mechanical Operations Counter

GMCNR

ACB Lifting Truck

ACBLIFT

Contact factory for availability.


Cassette/Substructure
The drawout mechanism allows the breaker to be racked
in four distinct positions:

CONNECTED

TEST

DISCONNECTED

WITHDRAWN


Position Indicators
Position indicators provide a positive mechanical
indication of CONNECTED, TEST and DISCONNECTED
positions of the breaker.

Rejection Device
A factory-installed rejection feature prevents mis-
matching breakers and cassettes/substructures. This
prevents:

Inserting a breaker with a lower rating into a higher
rated cassette/substructure.

Inserting a higher rated breaker into a lower rated
cassette/substructure.


Front Flat Terminations
The EntelliGuard G Fixed mounted breaker comes
standard with Back Connected Terminations. Optional
Front Flat terminations are available for front access
mounting (Table 6.24).
Table 6.24. Optional Front Flat Terminations

Description

Catalog

Number

Env1 800 - 2000A, Type N&H, Flat Front UL489
Fixed 3 Pole Breaker Bus Bar Terminations
(Top/Bottom)

GBB1TBF3

Env1 800 - 2000A, Type N&H, Flat Front UL489
Fixed 4 Pole Breaker Bus Bar Terminations
(Top/Bottom)

GBB1TBF4

Env2 800A - 3000A Flat Front UL489 Fixed 3
Pole Breaker Bus Bar Terminations
(Top/Bottom)

GBB2TBF3

Env2 800A - 3000A Flat Front UL489 Fixed 4
Pole Breaker Bus Bar Terminations
(Top/Bottom)

GBB2TBF4

Env3 4000-6000A Flat Front UL Fixed 3 Pole
Breaker Bus Bar Terminations (Top/Bottom)

GBB3TBF3

Env3 4000-6000A Flat Front UL Fixed 4 Pole
Breaker Bus Bar Terminations (Top/Bottom)

GBB3TBF4

Advertising