User administration

20

4

The “Master HMI” check box designates the primary HMI. When it is checked:

• The HMI have the functions of the “Local HMI”
• Send alarm emails via SNTP
• Operate Reduced Energy Let - Thru Mode (RELT)

Remote HMI Role

The Remote HMI software which can be installed on a standard workstation or laptop. There are
some minor differences between the Remote HMI and the Local HMI.

• The Local and Master HMI controls are disabled
• Does not send out email notifications for alarms
• Does not have ability to block breaker commands
• Uses port 502 for Modbus TCP/IP communication with CPUs
• Does not update time and time zone bias information of the CPUs

Communication restrictions

The CPUs can support up to 8 simultaneous communication ports for Modbus clients. Once the
limit is exceeded, clients will be blocked until a port is free. The Local HMIs have special ports
reserved for its use.

To set an Local HMI as a “Master”
1.
On the Main Menu, click the Maintenance button. The button will only be displayed if access

is allowed with the current login permissions.

2. Click the Modbus Security tab.
3. Select the Master check box as shown in Figure 4-5.
4. Click the OK button to save changes (or click Cancel to cancel changes).