Establishing communication to remote hmis, 1 network re-configuration procedure, 1 prepare the local network – GE Industrial Solutions Entellisys 5.0 Administrator Manual User Manual

Page 41: 7establishing communication to remote hmis

Advertising
background image

Network re-configuration procedure

41

7

7

Establishing communication to Remote

HMIs

The Entellisys system can be configured to communicate with up to 4 remote HMI PCs and 4
local HMI kiosked PanelC computers. The HMIs and CPUs all communicate through TCP/IP, and
by default, these devices are configured with IP addresses that work together on the local
network but will not communicate over a building network.

In general there are two methods to configure a Remote HMI workstation

A separate dedicated network: A second network card is installed in the Remote HMI

PCs which are connected to and configured for the Entellisys Network

Utilize the building LAN: The Entellisys system is configured to communicate on the

building LAN

NOTE: In either case, VPNs must be installed to protect the Entellisys network from network
traffic, unauthorized access and viruses. Failing to do so will put the entire system at risk!

7.1 Network re-configuration procedure

The following procedure must be done at the dedicated Kiosked PanelC HMI either in or near the
gear. The procedure must also be done before connecting to the building LAN. “Local” refers to
Entellisys network in the gear which the HMIs or CPUs are connected.

7.1.1 Prepare the local network

Step 1: Since Entellisys components are not DHCP-compatible, each device must be assigned a
static IP addresses which compatible on the company network

The number of IP addresses required depends on the number of HMIs. The following number of
IP addresses is required:

• 2 addresses for CPU A and CPU B
• Addresses for all In-Gear and Near-Gear HMIs
• 2 addresses for the Juniper 5GT VPN

Step 2: Reset the CPU IP Addresses (See

Changing the CPU IP address on page 42

)

Step 3: Reset the local HMI IP Addresses (See

Changing the local HMI IP address on page 43

)

Step 4: Verify communication between the local HMIs and CPUs (See

Verify local communication

to CPU on page 44

)

Step 5: Install and Configure a network security device such as a VPN/Firewall appliance (See

Network security/VPN device on page 45

)

Advertising